Can I solder 12/2 Romex to extend wire 5 ft?












5















I'm sure this is going to be lambasted by the code gods, but is it SAFE to solder the wires in a Romex cable to extend it? Obviously I would ground the circuit as normal, just trying to avoid another junction box. Would I heat shrink each individual wire and then the outer sheathing as well? Thanks for any advice










share|improve this question







New contributor




BigLake is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.
















  • 1





    Possible duplicate of Can cable splice devices be concealed?

    – JPhi1618
    10 hours ago






  • 4





    Solder, whether leaded or ROHS, introduces amalgam material into the joint. This material is subject to electromigration under current and ion diffusion without current, the different ion species will diffuse/migrate at different rates and directions to create distinct layers of homogenous material, the joints between these layers are brittle, resistive, and a source of mechanical weakness. This process takes 10+ Years to happen. Welding does not have this downside.

    – crasic
    7 hours ago













  • Why not pull a longer cable through?

    – LShaver
    1 min ago
















5















I'm sure this is going to be lambasted by the code gods, but is it SAFE to solder the wires in a Romex cable to extend it? Obviously I would ground the circuit as normal, just trying to avoid another junction box. Would I heat shrink each individual wire and then the outer sheathing as well? Thanks for any advice










share|improve this question







New contributor




BigLake is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.
















  • 1





    Possible duplicate of Can cable splice devices be concealed?

    – JPhi1618
    10 hours ago






  • 4





    Solder, whether leaded or ROHS, introduces amalgam material into the joint. This material is subject to electromigration under current and ion diffusion without current, the different ion species will diffuse/migrate at different rates and directions to create distinct layers of homogenous material, the joints between these layers are brittle, resistive, and a source of mechanical weakness. This process takes 10+ Years to happen. Welding does not have this downside.

    – crasic
    7 hours ago













  • Why not pull a longer cable through?

    – LShaver
    1 min ago














5












5








5


1






I'm sure this is going to be lambasted by the code gods, but is it SAFE to solder the wires in a Romex cable to extend it? Obviously I would ground the circuit as normal, just trying to avoid another junction box. Would I heat shrink each individual wire and then the outer sheathing as well? Thanks for any advice










share|improve this question







New contributor




BigLake is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.












I'm sure this is going to be lambasted by the code gods, but is it SAFE to solder the wires in a Romex cable to extend it? Obviously I would ground the circuit as normal, just trying to avoid another junction box. Would I heat shrink each individual wire and then the outer sheathing as well? Thanks for any advice







electrical soldering






share|improve this question







New contributor




BigLake is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











share|improve this question







New contributor




BigLake is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









share|improve this question




share|improve this question






New contributor




BigLake is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









asked 10 hours ago









BigLakeBigLake

526




526




New contributor




BigLake is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





New contributor





BigLake is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.






BigLake is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.








  • 1





    Possible duplicate of Can cable splice devices be concealed?

    – JPhi1618
    10 hours ago






  • 4





    Solder, whether leaded or ROHS, introduces amalgam material into the joint. This material is subject to electromigration under current and ion diffusion without current, the different ion species will diffuse/migrate at different rates and directions to create distinct layers of homogenous material, the joints between these layers are brittle, resistive, and a source of mechanical weakness. This process takes 10+ Years to happen. Welding does not have this downside.

    – crasic
    7 hours ago













  • Why not pull a longer cable through?

    – LShaver
    1 min ago














  • 1





    Possible duplicate of Can cable splice devices be concealed?

    – JPhi1618
    10 hours ago






  • 4





    Solder, whether leaded or ROHS, introduces amalgam material into the joint. This material is subject to electromigration under current and ion diffusion without current, the different ion species will diffuse/migrate at different rates and directions to create distinct layers of homogenous material, the joints between these layers are brittle, resistive, and a source of mechanical weakness. This process takes 10+ Years to happen. Welding does not have this downside.

    – crasic
    7 hours ago













  • Why not pull a longer cable through?

    – LShaver
    1 min ago








1




1





Possible duplicate of Can cable splice devices be concealed?

– JPhi1618
10 hours ago





Possible duplicate of Can cable splice devices be concealed?

– JPhi1618
10 hours ago




4




4





Solder, whether leaded or ROHS, introduces amalgam material into the joint. This material is subject to electromigration under current and ion diffusion without current, the different ion species will diffuse/migrate at different rates and directions to create distinct layers of homogenous material, the joints between these layers are brittle, resistive, and a source of mechanical weakness. This process takes 10+ Years to happen. Welding does not have this downside.

– crasic
7 hours ago







Solder, whether leaded or ROHS, introduces amalgam material into the joint. This material is subject to electromigration under current and ion diffusion without current, the different ion species will diffuse/migrate at different rates and directions to create distinct layers of homogenous material, the joints between these layers are brittle, resistive, and a source of mechanical weakness. This process takes 10+ Years to happen. Welding does not have this downside.

– crasic
7 hours ago















Why not pull a longer cable through?

– LShaver
1 min ago





Why not pull a longer cable through?

– LShaver
1 min ago










3 Answers
3






active

oldest

votes


















12














They do make Romex Splice Kits that claim to be legal for rework inside of a finished wall without junction boxes. Soldering is absolutely the wrong way, and regular wire nuts are not going to cut it. You need a mechanical fastener rated and tested for the job.



enter image description here






share|improve this answer
























  • Here is another question/answer discussing these devices: diy.stackexchange.com/q/89945/43874

    – JPhi1618
    10 hours ago











  • Excellent, I hadn't seen one of these. Thank you for the suggestion. I'll probably go with that.

    – BigLake
    10 hours ago






  • 3





    @JoeDunigan, Just keep in mind that it should be a last resort. If there's any possibility of replacing the whole run of cable, you really should do that. These splices are only meant for "repair" where running new wire would be very difficult.

    – JPhi1618
    10 hours ago






  • 1





    There are crimped-and-soldered knob & tube splices that are over 100 years old and as good as the day they were made. The main problem with the old K&T wiring is that the bare wires overheat when they get buried in insulation, and the rubber insulation dries out and falls apart. The problems with solder are, first, that it isn't legal, and also that the skill level of the home installer isn't remotely guaranteed, plus the vinyl insulation on today's wires is more likely to melt than the rubber insulation used in the old days was when the wire is heated with the soldering iron or torch, etc.

    – Craig
    8 hours ago



















8














Well, they actually make an approved device to splice Romex outside a junction box.



enter image description here



That said, soldering has very specific requirements for splicing it "dry" in advance before solder is even applied (this is a much bigger PitA than you think, because it makes tinning hard!) The splice connection must be both mechanically and electrically complete before you even start soldering. This is called out in NEC 110.14b.



Then you have to wrap and layer insulation in a particular way. I could see where shrink tube could be an option, but any sharp points on the resulting splice will tend to pierce the shrink tube, so I would do 2-3 layers of it over friction tape honestly. Friction tape does something electrical tape does not, and that's protect the insulation from physical damage from corners in the splice.



It is an artisanal craft, exactly the kind of reason why electricians are apprenticeships. Last time I did one, it took a half hour (per wire) and I'm still not confident it's right.





This is not kid stuff. Aside from the fact that you're supposed to pull permits and have inspections... fires get investigated. If it's found to be your negligence, fire insurance won't pay. Then the mortgage lender will call the note.



Every bit of Code I've ever seen, I have ultimately found had very good reasons for being that way. Code is written in blood and ash, it is the collective knowledge of how not to have problems unnecessarily.



With rare exception I have never seen a code violation that also managed to be safe. Those exceptions can be negotiated with your AHJ.






share|improve this answer





















  • 1





    Not at all, I'm quite aware and respectful of codes. In fact I oversized everything I did with my plumbing. I am new to wiring and have spent hours on sites like these and talking to friends with experience and electricians about how to do the job safely and effectively. Which is why I asked this question rather than just doing something that I know I COULD do but not knowing the full implications and possible effects. The only reason was I was looking for a way around a jbox for aesthetics, knowing that mechanical connections require them. Just wondering if there was another way.

    – BigLake
    10 hours ago











  • But thank you for your assumption that I'm snubbing codes and people that create them. That's why I used this site to ask, isn't that what it's for?

    – BigLake
    10 hours ago






  • 3





    @JoeDunigan I've toned it down. But we get a lot of people come in here going "Code seems stupid to me and I don't plan to follow it". Sorry if I mistook you for that, but you kinda sounded like that coming in.

    – Harper
    10 hours ago






  • 1





    @Harper I for one appreciate you making the point about the electrical code. Sure, it's conservative, but it is meant to be. The point is to prevent people from dying in avoidable fires caused by faulty installations (and also from electrocution). Besides, the code actually the law.

    – Craig
    8 hours ago






  • 1





    @Craig, just to be clear, the National Electrical Code is not a law. Many jurisdictions adopt a specific version of the NEC into their local laws, though, sometimes with regional variations or additions. My town uses the 2014 NEC with amendments, although they are hoping to adopt the 2017 code soon. [1]:

    – Medievalist
    6 hours ago





















4














Take a step back and consider. The right way to do it would have three distinct components: (a) wirenuts, (b) a box, and (c) accessibility behind a removable faceplate. The last of these is presumably what's causing trouble in this case. Why change the other two components too? Once you've decided you'll compromise code compliance, why not make the minimum possible deviation?



If I were reno'ing a house and found a box buried behind drywall, but it was a code-legal covered box and the connections were properly wire nutted, I'd say, Someone was lazy, and I would not have done it, but I understand, and I really could not say that a functional risk was created. If I found heatshrink-wrapped solder joints, I'd say someone went out of their way to show contempt for code, all current practices, and safety.



And it's not just that the code writers didn't know about solder. It turns out that in short-circuit high-current conditions, solder can melt or even evaporate very quickly, leaving you with no path to ground, or a high-resistance connection. Both very bad.






share|improve this answer























    Your Answer








    StackExchange.ready(function() {
    var channelOptions = {
    tags: "".split(" "),
    id: "73"
    };
    initTagRenderer("".split(" "), "".split(" "), channelOptions);

    StackExchange.using("externalEditor", function() {
    // Have to fire editor after snippets, if snippets enabled
    if (StackExchange.settings.snippets.snippetsEnabled) {
    StackExchange.using("snippets", function() {
    createEditor();
    });
    }
    else {
    createEditor();
    }
    });

    function createEditor() {
    StackExchange.prepareEditor({
    heartbeatType: 'answer',
    autoActivateHeartbeat: false,
    convertImagesToLinks: false,
    noModals: true,
    showLowRepImageUploadWarning: true,
    reputationToPostImages: null,
    bindNavPrevention: true,
    postfix: "",
    imageUploader: {
    brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
    contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
    allowUrls: true
    },
    noCode: true, onDemand: true,
    discardSelector: ".discard-answer"
    ,immediatelyShowMarkdownHelp:true
    });


    }
    });






    BigLake is a new contributor. Be nice, and check out our Code of Conduct.










    draft saved

    draft discarded


















    StackExchange.ready(
    function () {
    StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f159229%2fcan-i-solder-12-2-romex-to-extend-wire-5-ft%23new-answer', 'question_page');
    }
    );

    Post as a guest















    Required, but never shown

























    3 Answers
    3






    active

    oldest

    votes








    3 Answers
    3






    active

    oldest

    votes









    active

    oldest

    votes






    active

    oldest

    votes









    12














    They do make Romex Splice Kits that claim to be legal for rework inside of a finished wall without junction boxes. Soldering is absolutely the wrong way, and regular wire nuts are not going to cut it. You need a mechanical fastener rated and tested for the job.



    enter image description here






    share|improve this answer
























    • Here is another question/answer discussing these devices: diy.stackexchange.com/q/89945/43874

      – JPhi1618
      10 hours ago











    • Excellent, I hadn't seen one of these. Thank you for the suggestion. I'll probably go with that.

      – BigLake
      10 hours ago






    • 3





      @JoeDunigan, Just keep in mind that it should be a last resort. If there's any possibility of replacing the whole run of cable, you really should do that. These splices are only meant for "repair" where running new wire would be very difficult.

      – JPhi1618
      10 hours ago






    • 1





      There are crimped-and-soldered knob & tube splices that are over 100 years old and as good as the day they were made. The main problem with the old K&T wiring is that the bare wires overheat when they get buried in insulation, and the rubber insulation dries out and falls apart. The problems with solder are, first, that it isn't legal, and also that the skill level of the home installer isn't remotely guaranteed, plus the vinyl insulation on today's wires is more likely to melt than the rubber insulation used in the old days was when the wire is heated with the soldering iron or torch, etc.

      – Craig
      8 hours ago
















    12














    They do make Romex Splice Kits that claim to be legal for rework inside of a finished wall without junction boxes. Soldering is absolutely the wrong way, and regular wire nuts are not going to cut it. You need a mechanical fastener rated and tested for the job.



    enter image description here






    share|improve this answer
























    • Here is another question/answer discussing these devices: diy.stackexchange.com/q/89945/43874

      – JPhi1618
      10 hours ago











    • Excellent, I hadn't seen one of these. Thank you for the suggestion. I'll probably go with that.

      – BigLake
      10 hours ago






    • 3





      @JoeDunigan, Just keep in mind that it should be a last resort. If there's any possibility of replacing the whole run of cable, you really should do that. These splices are only meant for "repair" where running new wire would be very difficult.

      – JPhi1618
      10 hours ago






    • 1





      There are crimped-and-soldered knob & tube splices that are over 100 years old and as good as the day they were made. The main problem with the old K&T wiring is that the bare wires overheat when they get buried in insulation, and the rubber insulation dries out and falls apart. The problems with solder are, first, that it isn't legal, and also that the skill level of the home installer isn't remotely guaranteed, plus the vinyl insulation on today's wires is more likely to melt than the rubber insulation used in the old days was when the wire is heated with the soldering iron or torch, etc.

      – Craig
      8 hours ago














    12












    12








    12







    They do make Romex Splice Kits that claim to be legal for rework inside of a finished wall without junction boxes. Soldering is absolutely the wrong way, and regular wire nuts are not going to cut it. You need a mechanical fastener rated and tested for the job.



    enter image description here






    share|improve this answer













    They do make Romex Splice Kits that claim to be legal for rework inside of a finished wall without junction boxes. Soldering is absolutely the wrong way, and regular wire nuts are not going to cut it. You need a mechanical fastener rated and tested for the job.



    enter image description here







    share|improve this answer












    share|improve this answer



    share|improve this answer










    answered 10 hours ago









    JPhi1618JPhi1618

    8,80612142




    8,80612142













    • Here is another question/answer discussing these devices: diy.stackexchange.com/q/89945/43874

      – JPhi1618
      10 hours ago











    • Excellent, I hadn't seen one of these. Thank you for the suggestion. I'll probably go with that.

      – BigLake
      10 hours ago






    • 3





      @JoeDunigan, Just keep in mind that it should be a last resort. If there's any possibility of replacing the whole run of cable, you really should do that. These splices are only meant for "repair" where running new wire would be very difficult.

      – JPhi1618
      10 hours ago






    • 1





      There are crimped-and-soldered knob & tube splices that are over 100 years old and as good as the day they were made. The main problem with the old K&T wiring is that the bare wires overheat when they get buried in insulation, and the rubber insulation dries out and falls apart. The problems with solder are, first, that it isn't legal, and also that the skill level of the home installer isn't remotely guaranteed, plus the vinyl insulation on today's wires is more likely to melt than the rubber insulation used in the old days was when the wire is heated with the soldering iron or torch, etc.

      – Craig
      8 hours ago



















    • Here is another question/answer discussing these devices: diy.stackexchange.com/q/89945/43874

      – JPhi1618
      10 hours ago











    • Excellent, I hadn't seen one of these. Thank you for the suggestion. I'll probably go with that.

      – BigLake
      10 hours ago






    • 3





      @JoeDunigan, Just keep in mind that it should be a last resort. If there's any possibility of replacing the whole run of cable, you really should do that. These splices are only meant for "repair" where running new wire would be very difficult.

      – JPhi1618
      10 hours ago






    • 1





      There are crimped-and-soldered knob & tube splices that are over 100 years old and as good as the day they were made. The main problem with the old K&T wiring is that the bare wires overheat when they get buried in insulation, and the rubber insulation dries out and falls apart. The problems with solder are, first, that it isn't legal, and also that the skill level of the home installer isn't remotely guaranteed, plus the vinyl insulation on today's wires is more likely to melt than the rubber insulation used in the old days was when the wire is heated with the soldering iron or torch, etc.

      – Craig
      8 hours ago

















    Here is another question/answer discussing these devices: diy.stackexchange.com/q/89945/43874

    – JPhi1618
    10 hours ago





    Here is another question/answer discussing these devices: diy.stackexchange.com/q/89945/43874

    – JPhi1618
    10 hours ago













    Excellent, I hadn't seen one of these. Thank you for the suggestion. I'll probably go with that.

    – BigLake
    10 hours ago





    Excellent, I hadn't seen one of these. Thank you for the suggestion. I'll probably go with that.

    – BigLake
    10 hours ago




    3




    3





    @JoeDunigan, Just keep in mind that it should be a last resort. If there's any possibility of replacing the whole run of cable, you really should do that. These splices are only meant for "repair" where running new wire would be very difficult.

    – JPhi1618
    10 hours ago





    @JoeDunigan, Just keep in mind that it should be a last resort. If there's any possibility of replacing the whole run of cable, you really should do that. These splices are only meant for "repair" where running new wire would be very difficult.

    – JPhi1618
    10 hours ago




    1




    1





    There are crimped-and-soldered knob & tube splices that are over 100 years old and as good as the day they were made. The main problem with the old K&T wiring is that the bare wires overheat when they get buried in insulation, and the rubber insulation dries out and falls apart. The problems with solder are, first, that it isn't legal, and also that the skill level of the home installer isn't remotely guaranteed, plus the vinyl insulation on today's wires is more likely to melt than the rubber insulation used in the old days was when the wire is heated with the soldering iron or torch, etc.

    – Craig
    8 hours ago





    There are crimped-and-soldered knob & tube splices that are over 100 years old and as good as the day they were made. The main problem with the old K&T wiring is that the bare wires overheat when they get buried in insulation, and the rubber insulation dries out and falls apart. The problems with solder are, first, that it isn't legal, and also that the skill level of the home installer isn't remotely guaranteed, plus the vinyl insulation on today's wires is more likely to melt than the rubber insulation used in the old days was when the wire is heated with the soldering iron or torch, etc.

    – Craig
    8 hours ago













    8














    Well, they actually make an approved device to splice Romex outside a junction box.



    enter image description here



    That said, soldering has very specific requirements for splicing it "dry" in advance before solder is even applied (this is a much bigger PitA than you think, because it makes tinning hard!) The splice connection must be both mechanically and electrically complete before you even start soldering. This is called out in NEC 110.14b.



    Then you have to wrap and layer insulation in a particular way. I could see where shrink tube could be an option, but any sharp points on the resulting splice will tend to pierce the shrink tube, so I would do 2-3 layers of it over friction tape honestly. Friction tape does something electrical tape does not, and that's protect the insulation from physical damage from corners in the splice.



    It is an artisanal craft, exactly the kind of reason why electricians are apprenticeships. Last time I did one, it took a half hour (per wire) and I'm still not confident it's right.





    This is not kid stuff. Aside from the fact that you're supposed to pull permits and have inspections... fires get investigated. If it's found to be your negligence, fire insurance won't pay. Then the mortgage lender will call the note.



    Every bit of Code I've ever seen, I have ultimately found had very good reasons for being that way. Code is written in blood and ash, it is the collective knowledge of how not to have problems unnecessarily.



    With rare exception I have never seen a code violation that also managed to be safe. Those exceptions can be negotiated with your AHJ.






    share|improve this answer





















    • 1





      Not at all, I'm quite aware and respectful of codes. In fact I oversized everything I did with my plumbing. I am new to wiring and have spent hours on sites like these and talking to friends with experience and electricians about how to do the job safely and effectively. Which is why I asked this question rather than just doing something that I know I COULD do but not knowing the full implications and possible effects. The only reason was I was looking for a way around a jbox for aesthetics, knowing that mechanical connections require them. Just wondering if there was another way.

      – BigLake
      10 hours ago











    • But thank you for your assumption that I'm snubbing codes and people that create them. That's why I used this site to ask, isn't that what it's for?

      – BigLake
      10 hours ago






    • 3





      @JoeDunigan I've toned it down. But we get a lot of people come in here going "Code seems stupid to me and I don't plan to follow it". Sorry if I mistook you for that, but you kinda sounded like that coming in.

      – Harper
      10 hours ago






    • 1





      @Harper I for one appreciate you making the point about the electrical code. Sure, it's conservative, but it is meant to be. The point is to prevent people from dying in avoidable fires caused by faulty installations (and also from electrocution). Besides, the code actually the law.

      – Craig
      8 hours ago






    • 1





      @Craig, just to be clear, the National Electrical Code is not a law. Many jurisdictions adopt a specific version of the NEC into their local laws, though, sometimes with regional variations or additions. My town uses the 2014 NEC with amendments, although they are hoping to adopt the 2017 code soon. [1]:

      – Medievalist
      6 hours ago


















    8














    Well, they actually make an approved device to splice Romex outside a junction box.



    enter image description here



    That said, soldering has very specific requirements for splicing it "dry" in advance before solder is even applied (this is a much bigger PitA than you think, because it makes tinning hard!) The splice connection must be both mechanically and electrically complete before you even start soldering. This is called out in NEC 110.14b.



    Then you have to wrap and layer insulation in a particular way. I could see where shrink tube could be an option, but any sharp points on the resulting splice will tend to pierce the shrink tube, so I would do 2-3 layers of it over friction tape honestly. Friction tape does something electrical tape does not, and that's protect the insulation from physical damage from corners in the splice.



    It is an artisanal craft, exactly the kind of reason why electricians are apprenticeships. Last time I did one, it took a half hour (per wire) and I'm still not confident it's right.





    This is not kid stuff. Aside from the fact that you're supposed to pull permits and have inspections... fires get investigated. If it's found to be your negligence, fire insurance won't pay. Then the mortgage lender will call the note.



    Every bit of Code I've ever seen, I have ultimately found had very good reasons for being that way. Code is written in blood and ash, it is the collective knowledge of how not to have problems unnecessarily.



    With rare exception I have never seen a code violation that also managed to be safe. Those exceptions can be negotiated with your AHJ.






    share|improve this answer





















    • 1





      Not at all, I'm quite aware and respectful of codes. In fact I oversized everything I did with my plumbing. I am new to wiring and have spent hours on sites like these and talking to friends with experience and electricians about how to do the job safely and effectively. Which is why I asked this question rather than just doing something that I know I COULD do but not knowing the full implications and possible effects. The only reason was I was looking for a way around a jbox for aesthetics, knowing that mechanical connections require them. Just wondering if there was another way.

      – BigLake
      10 hours ago











    • But thank you for your assumption that I'm snubbing codes and people that create them. That's why I used this site to ask, isn't that what it's for?

      – BigLake
      10 hours ago






    • 3





      @JoeDunigan I've toned it down. But we get a lot of people come in here going "Code seems stupid to me and I don't plan to follow it". Sorry if I mistook you for that, but you kinda sounded like that coming in.

      – Harper
      10 hours ago






    • 1





      @Harper I for one appreciate you making the point about the electrical code. Sure, it's conservative, but it is meant to be. The point is to prevent people from dying in avoidable fires caused by faulty installations (and also from electrocution). Besides, the code actually the law.

      – Craig
      8 hours ago






    • 1





      @Craig, just to be clear, the National Electrical Code is not a law. Many jurisdictions adopt a specific version of the NEC into their local laws, though, sometimes with regional variations or additions. My town uses the 2014 NEC with amendments, although they are hoping to adopt the 2017 code soon. [1]:

      – Medievalist
      6 hours ago
















    8












    8








    8







    Well, they actually make an approved device to splice Romex outside a junction box.



    enter image description here



    That said, soldering has very specific requirements for splicing it "dry" in advance before solder is even applied (this is a much bigger PitA than you think, because it makes tinning hard!) The splice connection must be both mechanically and electrically complete before you even start soldering. This is called out in NEC 110.14b.



    Then you have to wrap and layer insulation in a particular way. I could see where shrink tube could be an option, but any sharp points on the resulting splice will tend to pierce the shrink tube, so I would do 2-3 layers of it over friction tape honestly. Friction tape does something electrical tape does not, and that's protect the insulation from physical damage from corners in the splice.



    It is an artisanal craft, exactly the kind of reason why electricians are apprenticeships. Last time I did one, it took a half hour (per wire) and I'm still not confident it's right.





    This is not kid stuff. Aside from the fact that you're supposed to pull permits and have inspections... fires get investigated. If it's found to be your negligence, fire insurance won't pay. Then the mortgage lender will call the note.



    Every bit of Code I've ever seen, I have ultimately found had very good reasons for being that way. Code is written in blood and ash, it is the collective knowledge of how not to have problems unnecessarily.



    With rare exception I have never seen a code violation that also managed to be safe. Those exceptions can be negotiated with your AHJ.






    share|improve this answer















    Well, they actually make an approved device to splice Romex outside a junction box.



    enter image description here



    That said, soldering has very specific requirements for splicing it "dry" in advance before solder is even applied (this is a much bigger PitA than you think, because it makes tinning hard!) The splice connection must be both mechanically and electrically complete before you even start soldering. This is called out in NEC 110.14b.



    Then you have to wrap and layer insulation in a particular way. I could see where shrink tube could be an option, but any sharp points on the resulting splice will tend to pierce the shrink tube, so I would do 2-3 layers of it over friction tape honestly. Friction tape does something electrical tape does not, and that's protect the insulation from physical damage from corners in the splice.



    It is an artisanal craft, exactly the kind of reason why electricians are apprenticeships. Last time I did one, it took a half hour (per wire) and I'm still not confident it's right.





    This is not kid stuff. Aside from the fact that you're supposed to pull permits and have inspections... fires get investigated. If it's found to be your negligence, fire insurance won't pay. Then the mortgage lender will call the note.



    Every bit of Code I've ever seen, I have ultimately found had very good reasons for being that way. Code is written in blood and ash, it is the collective knowledge of how not to have problems unnecessarily.



    With rare exception I have never seen a code violation that also managed to be safe. Those exceptions can be negotiated with your AHJ.







    share|improve this answer














    share|improve this answer



    share|improve this answer








    edited 9 hours ago

























    answered 10 hours ago









    HarperHarper

    72.5k448145




    72.5k448145








    • 1





      Not at all, I'm quite aware and respectful of codes. In fact I oversized everything I did with my plumbing. I am new to wiring and have spent hours on sites like these and talking to friends with experience and electricians about how to do the job safely and effectively. Which is why I asked this question rather than just doing something that I know I COULD do but not knowing the full implications and possible effects. The only reason was I was looking for a way around a jbox for aesthetics, knowing that mechanical connections require them. Just wondering if there was another way.

      – BigLake
      10 hours ago











    • But thank you for your assumption that I'm snubbing codes and people that create them. That's why I used this site to ask, isn't that what it's for?

      – BigLake
      10 hours ago






    • 3





      @JoeDunigan I've toned it down. But we get a lot of people come in here going "Code seems stupid to me and I don't plan to follow it". Sorry if I mistook you for that, but you kinda sounded like that coming in.

      – Harper
      10 hours ago






    • 1





      @Harper I for one appreciate you making the point about the electrical code. Sure, it's conservative, but it is meant to be. The point is to prevent people from dying in avoidable fires caused by faulty installations (and also from electrocution). Besides, the code actually the law.

      – Craig
      8 hours ago






    • 1





      @Craig, just to be clear, the National Electrical Code is not a law. Many jurisdictions adopt a specific version of the NEC into their local laws, though, sometimes with regional variations or additions. My town uses the 2014 NEC with amendments, although they are hoping to adopt the 2017 code soon. [1]:

      – Medievalist
      6 hours ago
















    • 1





      Not at all, I'm quite aware and respectful of codes. In fact I oversized everything I did with my plumbing. I am new to wiring and have spent hours on sites like these and talking to friends with experience and electricians about how to do the job safely and effectively. Which is why I asked this question rather than just doing something that I know I COULD do but not knowing the full implications and possible effects. The only reason was I was looking for a way around a jbox for aesthetics, knowing that mechanical connections require them. Just wondering if there was another way.

      – BigLake
      10 hours ago











    • But thank you for your assumption that I'm snubbing codes and people that create them. That's why I used this site to ask, isn't that what it's for?

      – BigLake
      10 hours ago






    • 3





      @JoeDunigan I've toned it down. But we get a lot of people come in here going "Code seems stupid to me and I don't plan to follow it". Sorry if I mistook you for that, but you kinda sounded like that coming in.

      – Harper
      10 hours ago






    • 1





      @Harper I for one appreciate you making the point about the electrical code. Sure, it's conservative, but it is meant to be. The point is to prevent people from dying in avoidable fires caused by faulty installations (and also from electrocution). Besides, the code actually the law.

      – Craig
      8 hours ago






    • 1





      @Craig, just to be clear, the National Electrical Code is not a law. Many jurisdictions adopt a specific version of the NEC into their local laws, though, sometimes with regional variations or additions. My town uses the 2014 NEC with amendments, although they are hoping to adopt the 2017 code soon. [1]:

      – Medievalist
      6 hours ago










    1




    1





    Not at all, I'm quite aware and respectful of codes. In fact I oversized everything I did with my plumbing. I am new to wiring and have spent hours on sites like these and talking to friends with experience and electricians about how to do the job safely and effectively. Which is why I asked this question rather than just doing something that I know I COULD do but not knowing the full implications and possible effects. The only reason was I was looking for a way around a jbox for aesthetics, knowing that mechanical connections require them. Just wondering if there was another way.

    – BigLake
    10 hours ago





    Not at all, I'm quite aware and respectful of codes. In fact I oversized everything I did with my plumbing. I am new to wiring and have spent hours on sites like these and talking to friends with experience and electricians about how to do the job safely and effectively. Which is why I asked this question rather than just doing something that I know I COULD do but not knowing the full implications and possible effects. The only reason was I was looking for a way around a jbox for aesthetics, knowing that mechanical connections require them. Just wondering if there was another way.

    – BigLake
    10 hours ago













    But thank you for your assumption that I'm snubbing codes and people that create them. That's why I used this site to ask, isn't that what it's for?

    – BigLake
    10 hours ago





    But thank you for your assumption that I'm snubbing codes and people that create them. That's why I used this site to ask, isn't that what it's for?

    – BigLake
    10 hours ago




    3




    3





    @JoeDunigan I've toned it down. But we get a lot of people come in here going "Code seems stupid to me and I don't plan to follow it". Sorry if I mistook you for that, but you kinda sounded like that coming in.

    – Harper
    10 hours ago





    @JoeDunigan I've toned it down. But we get a lot of people come in here going "Code seems stupid to me and I don't plan to follow it". Sorry if I mistook you for that, but you kinda sounded like that coming in.

    – Harper
    10 hours ago




    1




    1





    @Harper I for one appreciate you making the point about the electrical code. Sure, it's conservative, but it is meant to be. The point is to prevent people from dying in avoidable fires caused by faulty installations (and also from electrocution). Besides, the code actually the law.

    – Craig
    8 hours ago





    @Harper I for one appreciate you making the point about the electrical code. Sure, it's conservative, but it is meant to be. The point is to prevent people from dying in avoidable fires caused by faulty installations (and also from electrocution). Besides, the code actually the law.

    – Craig
    8 hours ago




    1




    1





    @Craig, just to be clear, the National Electrical Code is not a law. Many jurisdictions adopt a specific version of the NEC into their local laws, though, sometimes with regional variations or additions. My town uses the 2014 NEC with amendments, although they are hoping to adopt the 2017 code soon. [1]:

    – Medievalist
    6 hours ago







    @Craig, just to be clear, the National Electrical Code is not a law. Many jurisdictions adopt a specific version of the NEC into their local laws, though, sometimes with regional variations or additions. My town uses the 2014 NEC with amendments, although they are hoping to adopt the 2017 code soon. [1]:

    – Medievalist
    6 hours ago













    4














    Take a step back and consider. The right way to do it would have three distinct components: (a) wirenuts, (b) a box, and (c) accessibility behind a removable faceplate. The last of these is presumably what's causing trouble in this case. Why change the other two components too? Once you've decided you'll compromise code compliance, why not make the minimum possible deviation?



    If I were reno'ing a house and found a box buried behind drywall, but it was a code-legal covered box and the connections were properly wire nutted, I'd say, Someone was lazy, and I would not have done it, but I understand, and I really could not say that a functional risk was created. If I found heatshrink-wrapped solder joints, I'd say someone went out of their way to show contempt for code, all current practices, and safety.



    And it's not just that the code writers didn't know about solder. It turns out that in short-circuit high-current conditions, solder can melt or even evaporate very quickly, leaving you with no path to ground, or a high-resistance connection. Both very bad.






    share|improve this answer




























      4














      Take a step back and consider. The right way to do it would have three distinct components: (a) wirenuts, (b) a box, and (c) accessibility behind a removable faceplate. The last of these is presumably what's causing trouble in this case. Why change the other two components too? Once you've decided you'll compromise code compliance, why not make the minimum possible deviation?



      If I were reno'ing a house and found a box buried behind drywall, but it was a code-legal covered box and the connections were properly wire nutted, I'd say, Someone was lazy, and I would not have done it, but I understand, and I really could not say that a functional risk was created. If I found heatshrink-wrapped solder joints, I'd say someone went out of their way to show contempt for code, all current practices, and safety.



      And it's not just that the code writers didn't know about solder. It turns out that in short-circuit high-current conditions, solder can melt or even evaporate very quickly, leaving you with no path to ground, or a high-resistance connection. Both very bad.






      share|improve this answer


























        4












        4








        4







        Take a step back and consider. The right way to do it would have three distinct components: (a) wirenuts, (b) a box, and (c) accessibility behind a removable faceplate. The last of these is presumably what's causing trouble in this case. Why change the other two components too? Once you've decided you'll compromise code compliance, why not make the minimum possible deviation?



        If I were reno'ing a house and found a box buried behind drywall, but it was a code-legal covered box and the connections were properly wire nutted, I'd say, Someone was lazy, and I would not have done it, but I understand, and I really could not say that a functional risk was created. If I found heatshrink-wrapped solder joints, I'd say someone went out of their way to show contempt for code, all current practices, and safety.



        And it's not just that the code writers didn't know about solder. It turns out that in short-circuit high-current conditions, solder can melt or even evaporate very quickly, leaving you with no path to ground, or a high-resistance connection. Both very bad.






        share|improve this answer













        Take a step back and consider. The right way to do it would have three distinct components: (a) wirenuts, (b) a box, and (c) accessibility behind a removable faceplate. The last of these is presumably what's causing trouble in this case. Why change the other two components too? Once you've decided you'll compromise code compliance, why not make the minimum possible deviation?



        If I were reno'ing a house and found a box buried behind drywall, but it was a code-legal covered box and the connections were properly wire nutted, I'd say, Someone was lazy, and I would not have done it, but I understand, and I really could not say that a functional risk was created. If I found heatshrink-wrapped solder joints, I'd say someone went out of their way to show contempt for code, all current practices, and safety.



        And it's not just that the code writers didn't know about solder. It turns out that in short-circuit high-current conditions, solder can melt or even evaporate very quickly, leaving you with no path to ground, or a high-resistance connection. Both very bad.







        share|improve this answer












        share|improve this answer



        share|improve this answer










        answered 5 hours ago









        CCTOCCTO

        25112




        25112






















            BigLake is a new contributor. Be nice, and check out our Code of Conduct.










            draft saved

            draft discarded


















            BigLake is a new contributor. Be nice, and check out our Code of Conduct.













            BigLake is a new contributor. Be nice, and check out our Code of Conduct.












            BigLake is a new contributor. Be nice, and check out our Code of Conduct.
















            Thanks for contributing an answer to Home Improvement Stack Exchange!


            • Please be sure to answer the question. Provide details and share your research!

            But avoid



            • Asking for help, clarification, or responding to other answers.

            • Making statements based on opinion; back them up with references or personal experience.


            To learn more, see our tips on writing great answers.




            draft saved


            draft discarded














            StackExchange.ready(
            function () {
            StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f159229%2fcan-i-solder-12-2-romex-to-extend-wire-5-ft%23new-answer', 'question_page');
            }
            );

            Post as a guest















            Required, but never shown





















































            Required, but never shown














            Required, but never shown












            Required, but never shown







            Required, but never shown

































            Required, but never shown














            Required, but never shown












            Required, but never shown







            Required, but never shown







            Popular posts from this blog

            If I really need a card on my start hand, how many mulligans make sense? [duplicate]

            Alcedinidae

            Can an atomic nucleus contain both particles and antiparticles? [duplicate]