Why my Toroid Isolation Transformer has 112.3v to soil
I'm looking for a brand of Toroid isolation transformer with electrostatic shielding. There may be one brand which has this. Unless there is just none in the whole world? Is it not possible to put electrostatic shielding in any Toroid isolation transformer?
Original message (findings: It's a semi isolation transformer)
I bought a Hammond Isolation Transformer (dual 234v/117v primary and secondary) for isolating test projects from ground. But when I measured it from one of the output to the soil, it measures 112.3 volts. The other lead is near zero. I thought it was supposed to be isolated to ground.
Here's the model.
https://www.hammfg.com/electronics/transformers/power/1182.pdf
I chose the m117 model or 500va.
Here's the primary connection
Here's the secondary connection
Note all the 4 windings have no connection to each other initially (tested using continuity meter). Even after connecting them right. There is still no connection between primary and secondary (any of the wires), when not powered.
It's not an autotransformer which has connection between one of the leads of the primary and secondary. Unless a toroid autotransformer has no connections between the primary and secondary too?
So why does one of the leads reads 112.3 volts to the soil? Isn't it an isolation transformer? But the primary and secondary windings are supposed to be separate which is what makes isolation transformer, isn't it. What do you think?
An autotransformer only has one winding. The Hammond 1182 toroid has 4 windings. So how could it still be an autotransformer??
transformer
|
show 11 more comments
I'm looking for a brand of Toroid isolation transformer with electrostatic shielding. There may be one brand which has this. Unless there is just none in the whole world? Is it not possible to put electrostatic shielding in any Toroid isolation transformer?
Original message (findings: It's a semi isolation transformer)
I bought a Hammond Isolation Transformer (dual 234v/117v primary and secondary) for isolating test projects from ground. But when I measured it from one of the output to the soil, it measures 112.3 volts. The other lead is near zero. I thought it was supposed to be isolated to ground.
Here's the model.
https://www.hammfg.com/electronics/transformers/power/1182.pdf
I chose the m117 model or 500va.
Here's the primary connection
Here's the secondary connection
Note all the 4 windings have no connection to each other initially (tested using continuity meter). Even after connecting them right. There is still no connection between primary and secondary (any of the wires), when not powered.
It's not an autotransformer which has connection between one of the leads of the primary and secondary. Unless a toroid autotransformer has no connections between the primary and secondary too?
So why does one of the leads reads 112.3 volts to the soil? Isn't it an isolation transformer? But the primary and secondary windings are supposed to be separate which is what makes isolation transformer, isn't it. What do you think?
An autotransformer only has one winding. The Hammond 1182 toroid has 4 windings. So how could it still be an autotransformer??
transformer
3
"it measures 112.3 volts". But did you try to measure the resulting current? I bet it will be less than 100uA
– Ale..chenski
Dec 7 at 7:40
2
Nothing is perfect in real world :-(
– Ale..chenski
Dec 7 at 8:00
1
There is no "fully isolated" power sources. In this case there must be some DC coupling between primary and secondary, because it is possible that some high-frequency components of AC could be rectified over parasitic junctions and charge the secondary wires into kV area, which will be really dangerous. So some level of coupling is necessary for safety. And no, 100 uA won't give you any shock, although some tickling sensation is possible if you touch floating winding with your underarm.
– Ale..chenski
Dec 7 at 8:18
1
"If I accidentally touch the lead..." The Hammond probably sold these transformens to millions of people over nearly 100 years, and no one yet complained about any shock. Why don't you try to measure the actual current, and tell us?
– Ale..chenski
Dec 7 at 8:24
1
You don't need any "loads", just stick you DMM leads (in AC current mode) between the "semi-isolated" lead and ground.
– Ale..chenski
Dec 7 at 8:32
|
show 11 more comments
I'm looking for a brand of Toroid isolation transformer with electrostatic shielding. There may be one brand which has this. Unless there is just none in the whole world? Is it not possible to put electrostatic shielding in any Toroid isolation transformer?
Original message (findings: It's a semi isolation transformer)
I bought a Hammond Isolation Transformer (dual 234v/117v primary and secondary) for isolating test projects from ground. But when I measured it from one of the output to the soil, it measures 112.3 volts. The other lead is near zero. I thought it was supposed to be isolated to ground.
Here's the model.
https://www.hammfg.com/electronics/transformers/power/1182.pdf
I chose the m117 model or 500va.
Here's the primary connection
Here's the secondary connection
Note all the 4 windings have no connection to each other initially (tested using continuity meter). Even after connecting them right. There is still no connection between primary and secondary (any of the wires), when not powered.
It's not an autotransformer which has connection between one of the leads of the primary and secondary. Unless a toroid autotransformer has no connections between the primary and secondary too?
So why does one of the leads reads 112.3 volts to the soil? Isn't it an isolation transformer? But the primary and secondary windings are supposed to be separate which is what makes isolation transformer, isn't it. What do you think?
An autotransformer only has one winding. The Hammond 1182 toroid has 4 windings. So how could it still be an autotransformer??
transformer
I'm looking for a brand of Toroid isolation transformer with electrostatic shielding. There may be one brand which has this. Unless there is just none in the whole world? Is it not possible to put electrostatic shielding in any Toroid isolation transformer?
Original message (findings: It's a semi isolation transformer)
I bought a Hammond Isolation Transformer (dual 234v/117v primary and secondary) for isolating test projects from ground. But when I measured it from one of the output to the soil, it measures 112.3 volts. The other lead is near zero. I thought it was supposed to be isolated to ground.
Here's the model.
https://www.hammfg.com/electronics/transformers/power/1182.pdf
I chose the m117 model or 500va.
Here's the primary connection
Here's the secondary connection
Note all the 4 windings have no connection to each other initially (tested using continuity meter). Even after connecting them right. There is still no connection between primary and secondary (any of the wires), when not powered.
It's not an autotransformer which has connection between one of the leads of the primary and secondary. Unless a toroid autotransformer has no connections between the primary and secondary too?
So why does one of the leads reads 112.3 volts to the soil? Isn't it an isolation transformer? But the primary and secondary windings are supposed to be separate which is what makes isolation transformer, isn't it. What do you think?
An autotransformer only has one winding. The Hammond 1182 toroid has 4 windings. So how could it still be an autotransformer??
transformer
transformer
edited Dec 7 at 14:58
asked Dec 7 at 6:36
Jtl
476
476
3
"it measures 112.3 volts". But did you try to measure the resulting current? I bet it will be less than 100uA
– Ale..chenski
Dec 7 at 7:40
2
Nothing is perfect in real world :-(
– Ale..chenski
Dec 7 at 8:00
1
There is no "fully isolated" power sources. In this case there must be some DC coupling between primary and secondary, because it is possible that some high-frequency components of AC could be rectified over parasitic junctions and charge the secondary wires into kV area, which will be really dangerous. So some level of coupling is necessary for safety. And no, 100 uA won't give you any shock, although some tickling sensation is possible if you touch floating winding with your underarm.
– Ale..chenski
Dec 7 at 8:18
1
"If I accidentally touch the lead..." The Hammond probably sold these transformens to millions of people over nearly 100 years, and no one yet complained about any shock. Why don't you try to measure the actual current, and tell us?
– Ale..chenski
Dec 7 at 8:24
1
You don't need any "loads", just stick you DMM leads (in AC current mode) between the "semi-isolated" lead and ground.
– Ale..chenski
Dec 7 at 8:32
|
show 11 more comments
3
"it measures 112.3 volts". But did you try to measure the resulting current? I bet it will be less than 100uA
– Ale..chenski
Dec 7 at 7:40
2
Nothing is perfect in real world :-(
– Ale..chenski
Dec 7 at 8:00
1
There is no "fully isolated" power sources. In this case there must be some DC coupling between primary and secondary, because it is possible that some high-frequency components of AC could be rectified over parasitic junctions and charge the secondary wires into kV area, which will be really dangerous. So some level of coupling is necessary for safety. And no, 100 uA won't give you any shock, although some tickling sensation is possible if you touch floating winding with your underarm.
– Ale..chenski
Dec 7 at 8:18
1
"If I accidentally touch the lead..." The Hammond probably sold these transformens to millions of people over nearly 100 years, and no one yet complained about any shock. Why don't you try to measure the actual current, and tell us?
– Ale..chenski
Dec 7 at 8:24
1
You don't need any "loads", just stick you DMM leads (in AC current mode) between the "semi-isolated" lead and ground.
– Ale..chenski
Dec 7 at 8:32
3
3
"it measures 112.3 volts". But did you try to measure the resulting current? I bet it will be less than 100uA
– Ale..chenski
Dec 7 at 7:40
"it measures 112.3 volts". But did you try to measure the resulting current? I bet it will be less than 100uA
– Ale..chenski
Dec 7 at 7:40
2
2
Nothing is perfect in real world :-(
– Ale..chenski
Dec 7 at 8:00
Nothing is perfect in real world :-(
– Ale..chenski
Dec 7 at 8:00
1
1
There is no "fully isolated" power sources. In this case there must be some DC coupling between primary and secondary, because it is possible that some high-frequency components of AC could be rectified over parasitic junctions and charge the secondary wires into kV area, which will be really dangerous. So some level of coupling is necessary for safety. And no, 100 uA won't give you any shock, although some tickling sensation is possible if you touch floating winding with your underarm.
– Ale..chenski
Dec 7 at 8:18
There is no "fully isolated" power sources. In this case there must be some DC coupling between primary and secondary, because it is possible that some high-frequency components of AC could be rectified over parasitic junctions and charge the secondary wires into kV area, which will be really dangerous. So some level of coupling is necessary for safety. And no, 100 uA won't give you any shock, although some tickling sensation is possible if you touch floating winding with your underarm.
– Ale..chenski
Dec 7 at 8:18
1
1
"If I accidentally touch the lead..." The Hammond probably sold these transformens to millions of people over nearly 100 years, and no one yet complained about any shock. Why don't you try to measure the actual current, and tell us?
– Ale..chenski
Dec 7 at 8:24
"If I accidentally touch the lead..." The Hammond probably sold these transformens to millions of people over nearly 100 years, and no one yet complained about any shock. Why don't you try to measure the actual current, and tell us?
– Ale..chenski
Dec 7 at 8:24
1
1
You don't need any "loads", just stick you DMM leads (in AC current mode) between the "semi-isolated" lead and ground.
– Ale..chenski
Dec 7 at 8:32
You don't need any "loads", just stick you DMM leads (in AC current mode) between the "semi-isolated" lead and ground.
– Ale..chenski
Dec 7 at 8:32
|
show 11 more comments
2 Answers
2
active
oldest
votes
First, the 1182 series are not truly "isolation transformers". At least not on the linked datasheet. They are regular transformers with electrically unconnected secondary winding. While the secondary winding is not connected, the area of windings overlap is huge along the toroidal core, and thus there is capacitive coupling, since the whole thing operates on AC.
My take on the difference in readings is that by design, the windings are made in multiple layers, so one end is closer to primary winding, and the capacitive coupling is higher, while the other end is likely on the surface of the transformer, and has higher distance from primary winging.
The value of capacitive coupling could be 1 nF - 2 nF, which is about 3 MOhms, so a high-impedance DMM will see some AC voltage between floating leads and earth ground. And the effective leakage will be about 30 uA, which will be easily grounded once you connect it to your workbench ground.
True "line isolation transformers" usually include a single-layer winding (for toroidal core, and a non-shorted copper foil in rectangular bobbins, as Jeroen3 commented) with only one end exposed, which is connected to enclosure ground. In this case the cross-talk between primary coil and secondary coils is minimized, see Section "Line Transformers"
from main Hammond transformer catalog.
2
@jtl Yes it still isolates. It just has poor common mode. True safety isolation transformers only have capacitive coupling to earth due to a metal foil between primary and secondary winding.
– Jeroen3
Dec 7 at 7:44
1
@Jtl, the 240 model is of toroidal type, so windings still go over each other a lot. Good isolation transformer has coils on opposite sides of magnetic core, where the coupling is much less. Unless you demand coupling data from manufacturer, you shouldn't expect anything. Why a 100 uA leakage is bothering you?
– Ale..chenski
Dec 7 at 7:53
1
@jtl no. Still a toroidal. I have not seen those as isolation transformer. You need a normal iron core transformer with foil, or two separate coils.
– Jeroen3
Dec 7 at 7:54
2
@Jtl, it is getting more and more as "X-Y" problem. You are not telling why "strong magnetic field" is of any importance in "test projects", nor why 100 uA (easly grounded off) is of any concern.
– Ale..chenski
Dec 7 at 8:11
2
@Jtl, if you have special requirements as low magnetic interference, then encapsulate the entire transformer into a thick custom-made magnetic enclosure made of transformer steel or Nu Metal. No one will do it for you.
– Ale..chenski
Dec 7 at 8:27
|
show 8 more comments
Why do you assume it is not an autotransformer?
The 3rd bullet point of the pdf you linked contradicts what you stated:
Note: Units are designed to have all windings engaged (either series or parallel connected) or connected as an autotransformer.
In an autotransformer primary and secondary are connected.
EDIT:
I think Ale..chenski's answer is right.
Now I understand the sentence quoted above, that primary and secondary are isolated but the manufacturer assumes/suggests that the transfmormer will be connected by the user in such a way, that all windings are engaged or as autotransformer.
see imageshack.com/a/img923/6457/a4BM5X.gif An autotransformer only has one winding. The Hammond 1182 toroid has 4 windings. So how could it still be an autotransformer??
– Jtl
Dec 7 at 6:51
1
Maybe the diagram shows those 4 windings without the connection between them.
– Curd
Dec 7 at 6:56
Yes. But what does the phase "Note: Units are designed to have all windings engaged (either series or parallel connected) or connected as an autotransformer." mean? How could you have not any series or parallel connection and still have outputs? Any illustration?
– Jtl
Dec 7 at 7:04
2
Hi-Pot test of 4,000VAC RMS between primary & secondary
is not possible on a autotransformer.
– Jeroen3
Dec 7 at 7:41
So the 1182 is a semi isolation transformer? Would one get a shock if one accidentally touch one of the secondary output and ground?
– Jtl
Dec 7 at 8:16
|
show 7 more comments
Your Answer
StackExchange.ifUsing("editor", function () {
return StackExchange.using("mathjaxEditing", function () {
StackExchange.MarkdownEditor.creationCallbacks.add(function (editor, postfix) {
StackExchange.mathjaxEditing.prepareWmdForMathJax(editor, postfix, [["\$", "\$"]]);
});
});
}, "mathjax-editing");
StackExchange.ifUsing("editor", function () {
return StackExchange.using("schematics", function () {
StackExchange.schematics.init();
});
}, "cicuitlab");
StackExchange.ready(function() {
var channelOptions = {
tags: "".split(" "),
id: "135"
};
initTagRenderer("".split(" "), "".split(" "), channelOptions);
StackExchange.using("externalEditor", function() {
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled) {
StackExchange.using("snippets", function() {
createEditor();
});
}
else {
createEditor();
}
});
function createEditor() {
StackExchange.prepareEditor({
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader: {
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
},
onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
});
}
});
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2felectronics.stackexchange.com%2fquestions%2f410910%2fwhy-my-toroid-isolation-transformer-has-112-3v-to-soil%23new-answer', 'question_page');
}
);
Post as a guest
Required, but never shown
2 Answers
2
active
oldest
votes
2 Answers
2
active
oldest
votes
active
oldest
votes
active
oldest
votes
First, the 1182 series are not truly "isolation transformers". At least not on the linked datasheet. They are regular transformers with electrically unconnected secondary winding. While the secondary winding is not connected, the area of windings overlap is huge along the toroidal core, and thus there is capacitive coupling, since the whole thing operates on AC.
My take on the difference in readings is that by design, the windings are made in multiple layers, so one end is closer to primary winding, and the capacitive coupling is higher, while the other end is likely on the surface of the transformer, and has higher distance from primary winging.
The value of capacitive coupling could be 1 nF - 2 nF, which is about 3 MOhms, so a high-impedance DMM will see some AC voltage between floating leads and earth ground. And the effective leakage will be about 30 uA, which will be easily grounded once you connect it to your workbench ground.
True "line isolation transformers" usually include a single-layer winding (for toroidal core, and a non-shorted copper foil in rectangular bobbins, as Jeroen3 commented) with only one end exposed, which is connected to enclosure ground. In this case the cross-talk between primary coil and secondary coils is minimized, see Section "Line Transformers"
from main Hammond transformer catalog.
2
@jtl Yes it still isolates. It just has poor common mode. True safety isolation transformers only have capacitive coupling to earth due to a metal foil between primary and secondary winding.
– Jeroen3
Dec 7 at 7:44
1
@Jtl, the 240 model is of toroidal type, so windings still go over each other a lot. Good isolation transformer has coils on opposite sides of magnetic core, where the coupling is much less. Unless you demand coupling data from manufacturer, you shouldn't expect anything. Why a 100 uA leakage is bothering you?
– Ale..chenski
Dec 7 at 7:53
1
@jtl no. Still a toroidal. I have not seen those as isolation transformer. You need a normal iron core transformer with foil, or two separate coils.
– Jeroen3
Dec 7 at 7:54
2
@Jtl, it is getting more and more as "X-Y" problem. You are not telling why "strong magnetic field" is of any importance in "test projects", nor why 100 uA (easly grounded off) is of any concern.
– Ale..chenski
Dec 7 at 8:11
2
@Jtl, if you have special requirements as low magnetic interference, then encapsulate the entire transformer into a thick custom-made magnetic enclosure made of transformer steel or Nu Metal. No one will do it for you.
– Ale..chenski
Dec 7 at 8:27
|
show 8 more comments
First, the 1182 series are not truly "isolation transformers". At least not on the linked datasheet. They are regular transformers with electrically unconnected secondary winding. While the secondary winding is not connected, the area of windings overlap is huge along the toroidal core, and thus there is capacitive coupling, since the whole thing operates on AC.
My take on the difference in readings is that by design, the windings are made in multiple layers, so one end is closer to primary winding, and the capacitive coupling is higher, while the other end is likely on the surface of the transformer, and has higher distance from primary winging.
The value of capacitive coupling could be 1 nF - 2 nF, which is about 3 MOhms, so a high-impedance DMM will see some AC voltage between floating leads and earth ground. And the effective leakage will be about 30 uA, which will be easily grounded once you connect it to your workbench ground.
True "line isolation transformers" usually include a single-layer winding (for toroidal core, and a non-shorted copper foil in rectangular bobbins, as Jeroen3 commented) with only one end exposed, which is connected to enclosure ground. In this case the cross-talk between primary coil and secondary coils is minimized, see Section "Line Transformers"
from main Hammond transformer catalog.
2
@jtl Yes it still isolates. It just has poor common mode. True safety isolation transformers only have capacitive coupling to earth due to a metal foil between primary and secondary winding.
– Jeroen3
Dec 7 at 7:44
1
@Jtl, the 240 model is of toroidal type, so windings still go over each other a lot. Good isolation transformer has coils on opposite sides of magnetic core, where the coupling is much less. Unless you demand coupling data from manufacturer, you shouldn't expect anything. Why a 100 uA leakage is bothering you?
– Ale..chenski
Dec 7 at 7:53
1
@jtl no. Still a toroidal. I have not seen those as isolation transformer. You need a normal iron core transformer with foil, or two separate coils.
– Jeroen3
Dec 7 at 7:54
2
@Jtl, it is getting more and more as "X-Y" problem. You are not telling why "strong magnetic field" is of any importance in "test projects", nor why 100 uA (easly grounded off) is of any concern.
– Ale..chenski
Dec 7 at 8:11
2
@Jtl, if you have special requirements as low magnetic interference, then encapsulate the entire transformer into a thick custom-made magnetic enclosure made of transformer steel or Nu Metal. No one will do it for you.
– Ale..chenski
Dec 7 at 8:27
|
show 8 more comments
First, the 1182 series are not truly "isolation transformers". At least not on the linked datasheet. They are regular transformers with electrically unconnected secondary winding. While the secondary winding is not connected, the area of windings overlap is huge along the toroidal core, and thus there is capacitive coupling, since the whole thing operates on AC.
My take on the difference in readings is that by design, the windings are made in multiple layers, so one end is closer to primary winding, and the capacitive coupling is higher, while the other end is likely on the surface of the transformer, and has higher distance from primary winging.
The value of capacitive coupling could be 1 nF - 2 nF, which is about 3 MOhms, so a high-impedance DMM will see some AC voltage between floating leads and earth ground. And the effective leakage will be about 30 uA, which will be easily grounded once you connect it to your workbench ground.
True "line isolation transformers" usually include a single-layer winding (for toroidal core, and a non-shorted copper foil in rectangular bobbins, as Jeroen3 commented) with only one end exposed, which is connected to enclosure ground. In this case the cross-talk between primary coil and secondary coils is minimized, see Section "Line Transformers"
from main Hammond transformer catalog.
First, the 1182 series are not truly "isolation transformers". At least not on the linked datasheet. They are regular transformers with electrically unconnected secondary winding. While the secondary winding is not connected, the area of windings overlap is huge along the toroidal core, and thus there is capacitive coupling, since the whole thing operates on AC.
My take on the difference in readings is that by design, the windings are made in multiple layers, so one end is closer to primary winding, and the capacitive coupling is higher, while the other end is likely on the surface of the transformer, and has higher distance from primary winging.
The value of capacitive coupling could be 1 nF - 2 nF, which is about 3 MOhms, so a high-impedance DMM will see some AC voltage between floating leads and earth ground. And the effective leakage will be about 30 uA, which will be easily grounded once you connect it to your workbench ground.
True "line isolation transformers" usually include a single-layer winding (for toroidal core, and a non-shorted copper foil in rectangular bobbins, as Jeroen3 commented) with only one end exposed, which is connected to enclosure ground. In this case the cross-talk between primary coil and secondary coils is minimized, see Section "Line Transformers"
from main Hammond transformer catalog.
edited Dec 7 at 7:48
answered Dec 7 at 7:15
Ale..chenski
26.4k11863
26.4k11863
2
@jtl Yes it still isolates. It just has poor common mode. True safety isolation transformers only have capacitive coupling to earth due to a metal foil between primary and secondary winding.
– Jeroen3
Dec 7 at 7:44
1
@Jtl, the 240 model is of toroidal type, so windings still go over each other a lot. Good isolation transformer has coils on opposite sides of magnetic core, where the coupling is much less. Unless you demand coupling data from manufacturer, you shouldn't expect anything. Why a 100 uA leakage is bothering you?
– Ale..chenski
Dec 7 at 7:53
1
@jtl no. Still a toroidal. I have not seen those as isolation transformer. You need a normal iron core transformer with foil, or two separate coils.
– Jeroen3
Dec 7 at 7:54
2
@Jtl, it is getting more and more as "X-Y" problem. You are not telling why "strong magnetic field" is of any importance in "test projects", nor why 100 uA (easly grounded off) is of any concern.
– Ale..chenski
Dec 7 at 8:11
2
@Jtl, if you have special requirements as low magnetic interference, then encapsulate the entire transformer into a thick custom-made magnetic enclosure made of transformer steel or Nu Metal. No one will do it for you.
– Ale..chenski
Dec 7 at 8:27
|
show 8 more comments
2
@jtl Yes it still isolates. It just has poor common mode. True safety isolation transformers only have capacitive coupling to earth due to a metal foil between primary and secondary winding.
– Jeroen3
Dec 7 at 7:44
1
@Jtl, the 240 model is of toroidal type, so windings still go over each other a lot. Good isolation transformer has coils on opposite sides of magnetic core, where the coupling is much less. Unless you demand coupling data from manufacturer, you shouldn't expect anything. Why a 100 uA leakage is bothering you?
– Ale..chenski
Dec 7 at 7:53
1
@jtl no. Still a toroidal. I have not seen those as isolation transformer. You need a normal iron core transformer with foil, or two separate coils.
– Jeroen3
Dec 7 at 7:54
2
@Jtl, it is getting more and more as "X-Y" problem. You are not telling why "strong magnetic field" is of any importance in "test projects", nor why 100 uA (easly grounded off) is of any concern.
– Ale..chenski
Dec 7 at 8:11
2
@Jtl, if you have special requirements as low magnetic interference, then encapsulate the entire transformer into a thick custom-made magnetic enclosure made of transformer steel or Nu Metal. No one will do it for you.
– Ale..chenski
Dec 7 at 8:27
2
2
@jtl Yes it still isolates. It just has poor common mode. True safety isolation transformers only have capacitive coupling to earth due to a metal foil between primary and secondary winding.
– Jeroen3
Dec 7 at 7:44
@jtl Yes it still isolates. It just has poor common mode. True safety isolation transformers only have capacitive coupling to earth due to a metal foil between primary and secondary winding.
– Jeroen3
Dec 7 at 7:44
1
1
@Jtl, the 240 model is of toroidal type, so windings still go over each other a lot. Good isolation transformer has coils on opposite sides of magnetic core, where the coupling is much less. Unless you demand coupling data from manufacturer, you shouldn't expect anything. Why a 100 uA leakage is bothering you?
– Ale..chenski
Dec 7 at 7:53
@Jtl, the 240 model is of toroidal type, so windings still go over each other a lot. Good isolation transformer has coils on opposite sides of magnetic core, where the coupling is much less. Unless you demand coupling data from manufacturer, you shouldn't expect anything. Why a 100 uA leakage is bothering you?
– Ale..chenski
Dec 7 at 7:53
1
1
@jtl no. Still a toroidal. I have not seen those as isolation transformer. You need a normal iron core transformer with foil, or two separate coils.
– Jeroen3
Dec 7 at 7:54
@jtl no. Still a toroidal. I have not seen those as isolation transformer. You need a normal iron core transformer with foil, or two separate coils.
– Jeroen3
Dec 7 at 7:54
2
2
@Jtl, it is getting more and more as "X-Y" problem. You are not telling why "strong magnetic field" is of any importance in "test projects", nor why 100 uA (easly grounded off) is of any concern.
– Ale..chenski
Dec 7 at 8:11
@Jtl, it is getting more and more as "X-Y" problem. You are not telling why "strong magnetic field" is of any importance in "test projects", nor why 100 uA (easly grounded off) is of any concern.
– Ale..chenski
Dec 7 at 8:11
2
2
@Jtl, if you have special requirements as low magnetic interference, then encapsulate the entire transformer into a thick custom-made magnetic enclosure made of transformer steel or Nu Metal. No one will do it for you.
– Ale..chenski
Dec 7 at 8:27
@Jtl, if you have special requirements as low magnetic interference, then encapsulate the entire transformer into a thick custom-made magnetic enclosure made of transformer steel or Nu Metal. No one will do it for you.
– Ale..chenski
Dec 7 at 8:27
|
show 8 more comments
Why do you assume it is not an autotransformer?
The 3rd bullet point of the pdf you linked contradicts what you stated:
Note: Units are designed to have all windings engaged (either series or parallel connected) or connected as an autotransformer.
In an autotransformer primary and secondary are connected.
EDIT:
I think Ale..chenski's answer is right.
Now I understand the sentence quoted above, that primary and secondary are isolated but the manufacturer assumes/suggests that the transfmormer will be connected by the user in such a way, that all windings are engaged or as autotransformer.
see imageshack.com/a/img923/6457/a4BM5X.gif An autotransformer only has one winding. The Hammond 1182 toroid has 4 windings. So how could it still be an autotransformer??
– Jtl
Dec 7 at 6:51
1
Maybe the diagram shows those 4 windings without the connection between them.
– Curd
Dec 7 at 6:56
Yes. But what does the phase "Note: Units are designed to have all windings engaged (either series or parallel connected) or connected as an autotransformer." mean? How could you have not any series or parallel connection and still have outputs? Any illustration?
– Jtl
Dec 7 at 7:04
2
Hi-Pot test of 4,000VAC RMS between primary & secondary
is not possible on a autotransformer.
– Jeroen3
Dec 7 at 7:41
So the 1182 is a semi isolation transformer? Would one get a shock if one accidentally touch one of the secondary output and ground?
– Jtl
Dec 7 at 8:16
|
show 7 more comments
Why do you assume it is not an autotransformer?
The 3rd bullet point of the pdf you linked contradicts what you stated:
Note: Units are designed to have all windings engaged (either series or parallel connected) or connected as an autotransformer.
In an autotransformer primary and secondary are connected.
EDIT:
I think Ale..chenski's answer is right.
Now I understand the sentence quoted above, that primary and secondary are isolated but the manufacturer assumes/suggests that the transfmormer will be connected by the user in such a way, that all windings are engaged or as autotransformer.
see imageshack.com/a/img923/6457/a4BM5X.gif An autotransformer only has one winding. The Hammond 1182 toroid has 4 windings. So how could it still be an autotransformer??
– Jtl
Dec 7 at 6:51
1
Maybe the diagram shows those 4 windings without the connection between them.
– Curd
Dec 7 at 6:56
Yes. But what does the phase "Note: Units are designed to have all windings engaged (either series or parallel connected) or connected as an autotransformer." mean? How could you have not any series or parallel connection and still have outputs? Any illustration?
– Jtl
Dec 7 at 7:04
2
Hi-Pot test of 4,000VAC RMS between primary & secondary
is not possible on a autotransformer.
– Jeroen3
Dec 7 at 7:41
So the 1182 is a semi isolation transformer? Would one get a shock if one accidentally touch one of the secondary output and ground?
– Jtl
Dec 7 at 8:16
|
show 7 more comments
Why do you assume it is not an autotransformer?
The 3rd bullet point of the pdf you linked contradicts what you stated:
Note: Units are designed to have all windings engaged (either series or parallel connected) or connected as an autotransformer.
In an autotransformer primary and secondary are connected.
EDIT:
I think Ale..chenski's answer is right.
Now I understand the sentence quoted above, that primary and secondary are isolated but the manufacturer assumes/suggests that the transfmormer will be connected by the user in such a way, that all windings are engaged or as autotransformer.
Why do you assume it is not an autotransformer?
The 3rd bullet point of the pdf you linked contradicts what you stated:
Note: Units are designed to have all windings engaged (either series or parallel connected) or connected as an autotransformer.
In an autotransformer primary and secondary are connected.
EDIT:
I think Ale..chenski's answer is right.
Now I understand the sentence quoted above, that primary and secondary are isolated but the manufacturer assumes/suggests that the transfmormer will be connected by the user in such a way, that all windings are engaged or as autotransformer.
edited Dec 7 at 8:56
answered Dec 7 at 6:41
Curd
12.5k2232
12.5k2232
see imageshack.com/a/img923/6457/a4BM5X.gif An autotransformer only has one winding. The Hammond 1182 toroid has 4 windings. So how could it still be an autotransformer??
– Jtl
Dec 7 at 6:51
1
Maybe the diagram shows those 4 windings without the connection between them.
– Curd
Dec 7 at 6:56
Yes. But what does the phase "Note: Units are designed to have all windings engaged (either series or parallel connected) or connected as an autotransformer." mean? How could you have not any series or parallel connection and still have outputs? Any illustration?
– Jtl
Dec 7 at 7:04
2
Hi-Pot test of 4,000VAC RMS between primary & secondary
is not possible on a autotransformer.
– Jeroen3
Dec 7 at 7:41
So the 1182 is a semi isolation transformer? Would one get a shock if one accidentally touch one of the secondary output and ground?
– Jtl
Dec 7 at 8:16
|
show 7 more comments
see imageshack.com/a/img923/6457/a4BM5X.gif An autotransformer only has one winding. The Hammond 1182 toroid has 4 windings. So how could it still be an autotransformer??
– Jtl
Dec 7 at 6:51
1
Maybe the diagram shows those 4 windings without the connection between them.
– Curd
Dec 7 at 6:56
Yes. But what does the phase "Note: Units are designed to have all windings engaged (either series or parallel connected) or connected as an autotransformer." mean? How could you have not any series or parallel connection and still have outputs? Any illustration?
– Jtl
Dec 7 at 7:04
2
Hi-Pot test of 4,000VAC RMS between primary & secondary
is not possible on a autotransformer.
– Jeroen3
Dec 7 at 7:41
So the 1182 is a semi isolation transformer? Would one get a shock if one accidentally touch one of the secondary output and ground?
– Jtl
Dec 7 at 8:16
see imageshack.com/a/img923/6457/a4BM5X.gif An autotransformer only has one winding. The Hammond 1182 toroid has 4 windings. So how could it still be an autotransformer??
– Jtl
Dec 7 at 6:51
see imageshack.com/a/img923/6457/a4BM5X.gif An autotransformer only has one winding. The Hammond 1182 toroid has 4 windings. So how could it still be an autotransformer??
– Jtl
Dec 7 at 6:51
1
1
Maybe the diagram shows those 4 windings without the connection between them.
– Curd
Dec 7 at 6:56
Maybe the diagram shows those 4 windings without the connection between them.
– Curd
Dec 7 at 6:56
Yes. But what does the phase "Note: Units are designed to have all windings engaged (either series or parallel connected) or connected as an autotransformer." mean? How could you have not any series or parallel connection and still have outputs? Any illustration?
– Jtl
Dec 7 at 7:04
Yes. But what does the phase "Note: Units are designed to have all windings engaged (either series or parallel connected) or connected as an autotransformer." mean? How could you have not any series or parallel connection and still have outputs? Any illustration?
– Jtl
Dec 7 at 7:04
2
2
Hi-Pot test of 4,000VAC RMS between primary & secondary
is not possible on a autotransformer.– Jeroen3
Dec 7 at 7:41
Hi-Pot test of 4,000VAC RMS between primary & secondary
is not possible on a autotransformer.– Jeroen3
Dec 7 at 7:41
So the 1182 is a semi isolation transformer? Would one get a shock if one accidentally touch one of the secondary output and ground?
– Jtl
Dec 7 at 8:16
So the 1182 is a semi isolation transformer? Would one get a shock if one accidentally touch one of the secondary output and ground?
– Jtl
Dec 7 at 8:16
|
show 7 more comments
Thanks for contributing an answer to Electrical Engineering Stack Exchange!
- Please be sure to answer the question. Provide details and share your research!
But avoid …
- Asking for help, clarification, or responding to other answers.
- Making statements based on opinion; back them up with references or personal experience.
Use MathJax to format equations. MathJax reference.
To learn more, see our tips on writing great answers.
Some of your past answers have not been well-received, and you're in danger of being blocked from answering.
Please pay close attention to the following guidance:
- Please be sure to answer the question. Provide details and share your research!
But avoid …
- Asking for help, clarification, or responding to other answers.
- Making statements based on opinion; back them up with references or personal experience.
To learn more, see our tips on writing great answers.
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2felectronics.stackexchange.com%2fquestions%2f410910%2fwhy-my-toroid-isolation-transformer-has-112-3v-to-soil%23new-answer', 'question_page');
}
);
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
3
"it measures 112.3 volts". But did you try to measure the resulting current? I bet it will be less than 100uA
– Ale..chenski
Dec 7 at 7:40
2
Nothing is perfect in real world :-(
– Ale..chenski
Dec 7 at 8:00
1
There is no "fully isolated" power sources. In this case there must be some DC coupling between primary and secondary, because it is possible that some high-frequency components of AC could be rectified over parasitic junctions and charge the secondary wires into kV area, which will be really dangerous. So some level of coupling is necessary for safety. And no, 100 uA won't give you any shock, although some tickling sensation is possible if you touch floating winding with your underarm.
– Ale..chenski
Dec 7 at 8:18
1
"If I accidentally touch the lead..." The Hammond probably sold these transformens to millions of people over nearly 100 years, and no one yet complained about any shock. Why don't you try to measure the actual current, and tell us?
– Ale..chenski
Dec 7 at 8:24
1
You don't need any "loads", just stick you DMM leads (in AC current mode) between the "semi-isolated" lead and ground.
– Ale..chenski
Dec 7 at 8:32